OSI-R-SS Smoke Detector

An easy-to-install detector with only one side that needs wiring. 

Description:

OSI-R-SS is a 4-wire conventional reflector-type linear optical beam smoke detector for use in fire alarm systems. The beam operates primarily on the principle of light obscuration using an infrared beam. Optical beam smoke detectors are uniquely suited to protecting buildings with large open areas with high ceilings such as a warehouse or atrium. The OSI-R-SS detector is a combined transmitter/receiver unit that can be directly connected to a conventional detector circuit.

Product Features:

  • Combined transmitter/receiver unit
  • Wide 12° field of view
  • Fast, easy, and intuitive beam alignment indicated by directional LED crosshair arrows
  • Long range coverage of 5-100 m (16-328 ft) is standard; no separate long-range kit required
  • Highly resistant to building movement; tolerates +/- 1° movement
  • Resistant to strong light sources; does not alarm when saturated by sunlight
  • Resistant to solid object intrusion
  • Automatic sensitivity threshold level setting
  • 50° horizontal and 20° vertical beam adjustment
  • Built-in imager heater is standard
  • Remote test station capable for electronic simulated smoke test from ground level
  • Standby, fault and alarm LED indicators visible from the front and bottom
  • Automatic drift compensation
  • Paintable housing/cover
  • Removable plug-in terminal blocks
  • Optional heater kit available for the reflector

Technical Specifications:

PHYSICAL/OPERATING SPECIFICATIONS
Dimensions (Detector)Height 6” (152.4 mm); Width 10” (254 mm); Depth 4.5” (114.3 mm)
Dimensions (Reflector)Height 9.06” (230 mm); Width 7.87” (200 mm)
Weight (Installed)2.48 lbs (1.12 kg)
Weight (Shipping):3.91 lbs (1.77 kg)
Wire Gauge for Terminals14 AWG (2.08 mm2)
ELECTRICAL SPECIFICATIONS
Operating Voltage Range10.2 to 32 VDC (12 or 24VDC nominal)
Maximum Standby Current7 mA @ 32 VDC11 mA @ 24 VDC20 mA @ 12 VDC50 mA @ 10.2 VDC
Maximum Alarm Current11 mA @ 32 VDC15 mA @ 24 VDC24 mA @ 12 VDC54 mA @ 10.2 VDC
ENVIRONMENTAL SPECIFICATIONS
Operating Humidity Range0 to 95% Relative Humidity, Non-condensing
Operating Temperature RangeUL-Listed for use from 32°F to 100°F (0°C to 37.8°C)Application Temperature Range: -20°C to +55°C (-4°F to 131°F)
OPERATIONAL SPECIFICATIONS
Protection Range16 ft to 328 ft (5 m to 100 m)
Adjustment Angle20 degrees vertical, 50 degrees horizontal
Sensitivity LevelsLevel 1 25%, Level 2 30%, Level 3 40%, Level 4 50%
Fault Condition (Trouble)Long-term drift reference out of 20% range, beam blockage or detector out of alignment, imager saturated.
Alignment AidLED directional arrows
Alarm IndicatorLocal red LED and remote output
Trouble IndicatorLocal yellow LED and remote trouble output
Normal IndicatorLocal flashing green LED
Test/Reset FeaturesLocal alarm test switch, local alarm reset switch, Remote test and reset switch (Compatible with RTS151 and RTS151KEY(-A) test stations), Uses OSID-R test filter.
Smoke Detector SpacingOn smooth ceilings, 30-60 feet between projected beams and not more than one-half that spacing between a projected beam and a sidewall. Other spacing may be used dependingon the ceiling height, airflow characteristics, and response requirements. See NFPA 72 (S524 in Canadian applications).